Tagwright

Free checklist and calculator Fire extinguisher inspection checklist

What to check on every extinguisher each month, what annual and six-year maintenance cover, and when each type needs its hydrostatic test. Work out the next due dates below.

Monthly inspection

About every 30 days, a quick visual check of each extinguisher (NFPA 10, Chapter 7). Record the date and your initials on the tag or in your inspection record.

#CheckCommon failuresOK
1In its assigned place, visible and not blockedMoved, hidden behind stock or furniture, signage missing.
2Operating instructions legible and facing outLabel faded, peeling or turned to the wall.
3Safety pin and tamper seal in placePin missing or seal broken: it may have been used.
4Gauge in the operable range, or weight correctNeedle in the red, or a CO2 unit lighter than its stamped weight.
5No damage, corrosion, leaks or blocked nozzleDents, rust, leaking agent, a nozzle plugged by dirt or insects.
6Hose and nozzle in good conditionCracked or brittle hose, a loose or missing nozzle.
7Full, confirmed by weighing or heftingFeels light, or the agent has caked (dry chemical).
8Bracket or cabinet secure, correct heightLoose bracket, cabinet door jammed or glass broken.

Annual and six-year maintenance

Service intervals by type

Extinguisher typeHydrostatic testSix-year maintenance
ABC dry chemicalEvery 12 yearsYes
BC dry chemicalEvery 12 yearsYes
Carbon dioxide (CO2)Every 5 yearsNo
Water (APW)Every 5 yearsNo
Wet chemical (Class K)Every 5 yearsNo
Clean agentEvery 12 yearsYes
Foam (AFFF)Every 5 yearsNo
Dry powder (Class D)Every 12 yearsYes

Intervals also depend on how the extinguisher is built; check the nameplate and the manufacturer's manual.

Next due dates

Extinguisher
Six-year maintenance
2028
Hydrostatic test
2034

Due in the same month as the date on the label. Annual maintenance is due every year in that month too.

Questions

How often do fire extinguishers have to be inspected?

A quick visual inspection about every 30 days, annual maintenance by a certified technician, and depending on the type a six-year maintenance and a hydrostatic test every 5 or 12 years (NFPA 10, Chapters 7 and 8).

Who can do the monthly extinguisher inspection?

The building owner or someone they assign can do the monthly visual check and record it. Annual maintenance, six-year maintenance and hydrostatic testing are done by a certified service technician; many states also license extinguisher service companies.

What is the difference between inspection and maintenance?

The monthly inspection is a quick look to confirm the extinguisher is there, charged and undamaged. Maintenance is a thorough examination of the mechanical parts, the agent and the expelling means, done at least once a year and recorded on a service tag.

When is a hydrostatic test due?

Every 5 years for water, foam, wet chemical and CO2 extinguishers, and every 12 years for stored-pressure dry chemical, clean agent and dry powder units, counted from the date of manufacture or the last test marked on the cylinder.

What is the six-year maintenance?

Stored-pressure extinguishers with a 12-year hydrostatic test, such as ABC dry chemical, are emptied and examined internally every six years, then recharged. The clock restarts when the unit is hydrostatically tested.

What has to be recorded?

Monthly inspections need the date and the initials of the person who did them, on a tag or in an electronic record. Maintenance and tests are recorded on a tag or label with the month and year, the work done and who did it.

Our own summary of common NFPA 10 inspection and maintenance points, not the standard's text. Follow the edition adopted by the authority having jurisdiction and the manufacturer's manual.